MEASURING INSTRUMENT

HAL960 @yUltrasonic Level Meterz

Ultrasonic Level Meter

HAL960

Standard specification

Model No. HAL960
Number of channels 1CH
Frequency 12‚‹Hz
Object to be measured Liquid/Powder
Measurement distance range
(1/2 for powder)
1.5 to 60m
Resolution Measurement 5mm
Display 5mm
Accuracy }0.25%F.S. (}15cm)
Data update cycle 1.5sec.
Sensor directivity angle
ibeam anglej
14‹
Power supply Voltage AC85`264V(15VA)
Power consumption 15VA
Display LCD(with backlight)
Output Alarm output 4 lines
AC250V,DC30V 5A (Relay contact)
4-20mA current output
imaximum load resistancej
16bit
RL(MAX)=600Ħ
Interface RS-485
(Max.transmission rangeF1200‚j


Main unit Sensor
Operating ambient temperatures@@@ -20 to 60Ž
Material ABS@ PVC and other
Protection standard IP66 IP53
Dimensions(W~D~H) 185~85~235mm ƒÓ264~181mm
Sensor cable length - 5‚
Maximum sensor cable length - 200‚
Distribution cable length Not supplied -
Weight 1.8‚‹‚‡ 1k‚‡
Sensor attachment screwiold JISj - R1iPT1j


Features
¡Measures a wide range of distances:from 1.5 to 60 m
Ensures reliable measurements using the conical sensor.
¡Four alarm output lines are provided to enble various controls.
¡The RS-485 is provided as part of the standard configuration to enable remote control at a distance of up to 1,200 m.
The MODBUS protocol is provided as part of the standard configuration,enabling communications with a PLC.
¡The ultrasonic signals received are processed to reduce the effects of external noise and external ultrasonic waves.
¡Uses a conical sensor for compact dimensions and low weight.

Option

¡PROFIBUS communication converter

Individual Catalog

œIndividual catalog of HAL960 can be seen with PDF file. (The information of HAL960 has not yet posted to Measuring Instruments General Catalog.)

HAL960 Individual CatalogiPDFF618kbj


get Adobe PDF Install Adobe Reader to view the PDF file of this page.
Measuring Instrument TEL:81-532-41-2177 MAIL:keisoku@honda-el.co.jp